Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2021, 11:26 AM
  • 14 0026_14 0993_12282021_033149.mp4

Date
12/28/2021
W/O
926629
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01136
PipeID
P25748
Time
3:26 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9806
Sewer Name
14 ROSAMOND OUTFALL REPLACEMENT TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
03
Purpose
Routine Assessment
Project
WO_926629_TV14015_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 0026
Downstream MH
14 0993
Dir. of Survey
Downstream
Length Surveyed
22.3 ft.
Total Length
22.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 14 0026 to 14 0993
MH: 14 0026MH: 14 0993downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 00260 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start20.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish22.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK22.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0993

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
22.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
20.1DAGS
0AMH14 0026
22.3AMH14 0993
2DAGS
0MWM

Properties (8)

additional_info
630138122721202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-12-28T03:26:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39115