- Date
- 12/06/2021
- W/O
- 926698
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z01015
- PipeID
- P24135
- Time
- 12:44 PM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9292
- Sewer Name
- 29 EASTSIDE INTERCEPTOR SEWER
- City
- SIGNAL HILL
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 29
- Page No.
- 02
- Purpose
- Routine Assessment
- Project
- RFIR_WO_926698_TV29080_DEC2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 8 in.
- Upstream MH
- 29 0232
- Downstream MH
- 29 0063A
- Dir. of Survey
- Downstream
- Length Surveyed
- 164.7 ft.
- Total Length
- 164.7 ft.
- Structural Index
- 3
- Structural Quick
- 3311
- Structural Rating
- 10
- O&M Index
- 2
- O&M Quick
- 2E00
- O&M Rating
- 60
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 70
Pipe schematic from manhole 29 0232 to 29 0063A Observation photos (5)

15.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

95.6 ft. - Repair Pipe Replaced, within 8 inches of joint: YES, Start - CIP SEGMENT

106.5 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES

153 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

153 ft. - Joint Offset Medium