Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2021, 10:52 AM
  • 16 0514_16 0513_12152021_031408.mp4

Date
12/15/2021
W/O
926770
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00659
PipeID
P13565
Time
2:52 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9634
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_926770_TV16119_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0514
Downstream MH
16 0513
Dir. of Survey
Downstream
Length Surveyed
280.9 ft.
Total Length
280.9 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
15
O&M Index
2
O&M Quick
3122
O&M Rating
9
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 16 0514 to 16 0513
MH: 16 0514MH: 16 0513downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05140 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start40.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"63 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"89 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish100 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES102.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"102.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start122.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish137.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start163.2 ft. RFC - Roots Fine Connection, from 09 to 12 o'clock163.2 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"184 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES184 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"199.3 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES224.4 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"225.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start245 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES278.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish278.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish278.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish280.9 ft. AMH - Downstream Manhole, Survey Ends - 16 0513

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    3.5 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    100 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    102.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    137.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 09 to 12 o'clock

    163.2 ft. - Roots Fine Connection, from 09 to 12 o'clock

  • Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    184 ft. - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    199.3 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    225.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

    270.9 ft. - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
224.4TBA
225.2CM
0AMH16 0514
184RMC
63TBA
245TBA
270.9RFJ
137.4DAE
137.2CL
40.7TBA
278.8CM
100CM
2DAGS
102.1TBA
0MWM
278.8DAE
102.4CL
8FM
278.8DAGS
89FM
184TBA
163.2RFC
199.3CM
280.9AMH16 0513
163.2TBA
3.5TBA
0MWL
122.3TBA

Properties (7)

additional_info
630138121421203
custom_field_three
FRACTURES/CRACKS/ROOTS
custom_field_two
2
customer
1
datetime
2021-12-15T02:52:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false