Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2021, 08:58 AM
  • 18 0979_18 0978_12072021_010049.mp4

Date
12/07/2021
W/O
926407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00717
PipeID
P14830
Time
12:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9615
Sewer Name
18 WORSHAM CREEK RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Routine Assessment
Project
WO_926407_TV18061_DEC2021
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 0978
Downstream MH
18 0979
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0978 to 18 0979
MH: 18 0978MH: 18 0979upstream0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES2 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. MWL - Water Level, 95 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - 18 0978, EAST SIPHON

Observation photos (2)

  • Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.

  • Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
0MWM
2MSAVIEW OF UPLEG OF D/S EAST SIPHON.
2DAGS
0MWL
0AMH18 0978, EAST SIPHON

Properties (7)

additional_info
630138120621202
custom_field_three
HIGH WATER LEVEL
custom_field_two
5
customer
1
datetime
2021-12-07T00:58:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false