Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 18, 2022, 08:32 AM
  • 01 0325_01 0324_1182022_010203.mp4

Date
01/18/2022
W/O
0931893
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00215
PipeID
P00793
Time
12:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2083
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20220112MDM_NADEAU_TRUNK_SECTS_2_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
01 0324
Downstream MH
01 0325
Dir. of Survey
Upstream
Length Surveyed
484.9 ft.
Total Length
484.9 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 01 0324 to 01 0325
MH: 01 0324MH: 01 0325upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:40AM0.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR0.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN8.1 ft. MGP - General Photograph - CIRCUM REBAR CORRODED8.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR13.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC96.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC163.7 ft. MGO - General Observation - MAG COAT 60%184.3 ft. SAP - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG215.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC240.8 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SE4VERE AGG392.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG409.1 ft. SAV - Surface Aggregate Visible, from 01 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC459.8 ft. MGO - General Observation - 90% MAG COAT482.9 ft. MGO - General Observation - 70% MAG COAT482.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC482.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE484.9 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM484.9 ft. MWL - Water Level, 10 %of cross sectional area484.9 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (14)

  • General Observation - 70% MAG COAT

    2 ft. - General Observation - 70% MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 90% MAG COAT

    25.1 ft. - General Observation - 90% MAG COAT

  • Surface Aggregate Visible, from 01 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    75.8 ft. - Surface Aggregate Visible, from 01 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    92.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SE4VERE AGG

    244.1 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SE4VERE AGG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    269.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    300.6 ft. - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • General Observation - MAG COAT 60%

    321.2 ft. - General Observation - MAG COAT 60%

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    388.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    471.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Photograph - CIRCUM REBAR CORRODED

    476.8 ft. - General Photograph - CIRCUM REBAR CORRODED

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    476.8 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

Observations (24)

DistanceCodeObservation
476.8MGPCIRCUM REBAR CORRODED
484.3SRCCIRCUM REBAR
484.3SAPSEVERE AGG
25.1MGO90% MAG COAT
0AMH12:45AM
484.3SAMSEVERE AGG
244.1SAVSE4VERE AGG
75.8SAVSEVERE AGG SPORATIC
269.1SAPSEVERE AGG SPORATIC
0MWL
471.8SAMSEVERE AGG SPORATIC
2MGO70% MAG COAT
484.3SSSBLISTERING PEELING CONCRETE
476.8SRCCIRCUM REBAR
321.2MGOMAG COAT 60%
2SAVSEVERE AGG SPORATIC
92.4SAVSEVERE AGG
388.8SAMSEVERE AGG SPORATIC
300.6SAPSEVERE AGG
484.3SAVSEVERE AGG
484.9AMH1:40AM
484.3MGOConn. @ Mh, 3 O' Clock. OPEN
0MWM
2SSSBLISTERING PEELING CONCRETE

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED-60% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2022-01-18T00:32:33-08:00
documentation
MARTIN,REVELES,CASTILLO
is_lateral_inspection
false