Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2022, 12:19 PM
  • 01 0334_01 0333_1142022_042707.mp4

Date
01/14/2022
W/O
0931893
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00215
PipeID
P00804
Time
4:19 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2080
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20220112MDM_NADEAU_TRUNK_SECTS_2_1
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
01 0334
Downstream MH
01 0333
Dir. of Survey
Downstream
Length Surveyed
397.8 ft.
Total Length
397.8 ft.
Structural Index
3
Structural Quick
4123
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0334 to 01 0333
MH: 01 0334MH: 01 0333downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED19.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATT ACHED102.4 ft. MGO - General Observation - 25% MAG COAT START112.4 ft. MGO - General Observation - 60% MAG COAT START175.3 ft. MGO - General Observation - 75% MAG COATSTART397.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG397.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED397.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE397.8 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATT ACHED

    19.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATT ACHED

  • General Observation - 25% MAG COAT START

    102.4 ft. - General Observation - 25% MAG COAT START

  • General Observation - 60% MAG COAT START

    112.4 ft. - General Observation - 60% MAG COAT START

Observations (14)

DistanceCodeObservation
2SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG
112.4MGO60% MAG COAT START
175.3MGO75% MAG COATSTART
397.4SAMSEVERE AGG
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWL
0MWM
397.4SSSPEELING CONCRETE SEVERE AGG ATTACHED
397.8AMH5:00AM
19.5SSSPEELING CONCRETE SEVERE AGG ATT ACHED
0AMH4:30AM
102.4MGO25% MAG COAT START
397.4SSSBLISTERING PEELING CONCRETE

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2022-01-14T04:19:00-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false