Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2022, 10:08 AM
  • 01 0341_01 0340_1122022_031407.mp4

Date
01/12/2022
W/O
0931893
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00215
PipeID
P00813
Time
2:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2080
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20220112MDM_NADEAU_TRUNK_SECTS_2_1
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
01 0340
Downstream MH
01 0341
Dir. of Survey
Upstream
Length Surveyed
322.7 ft.
Total Length
322.7 ft.
Structural Index
3
Structural Quick
4222
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0340 to 01 0341
MH: 01 0340MH: 01 0341upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:50AM0.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED204.8 ft. MGO - General Observation - MAG COAT 50%START210 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG265.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATT ACHED275.9 ft. MGO - General Observation - 80% MAG COAT START320.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SVERE AGG320.7 ft. MGO - General Observation - MAG COAT 960% START320.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE322.7 ft. MWL - Water Level, 10 %of cross sectional area322.7 ft. AMH - Downstream Manhole, Survey Begins - 3:10AM322.7 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (7)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SVERE AGG

  • General Observation - MAG COAT 960% START

    2 ft. - General Observation - MAG COAT 960% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 80% MAG COAT START

    46.8 ft. - General Observation - 80% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATT ACHED

    57.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATT ACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    112.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - MAG COAT 50%START

    117.9 ft. - General Observation - MAG COAT 50%START

Observations (14)

DistanceCodeObservation
0MWL
46.8MGO80% MAG COAT START
322.2SAMSEVERE AGG
0AMH3:10AM
0MWM
2SAMSVERE AGG
322.2SSSBLISTERING PEELING CONCRETE
322.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
57.5SSSPEELING CONCRETE SEVERE AGG ATT ACHED
322.7AMH3:50AM
2MGOMAG COAT 960% START
2SSSBLISTERING PEELING CONCRETE
112.7SAMSEVERE AGG
117.9MGOMAG COAT 50%START

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED-50% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2022-01-12T02:08:42-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false