Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2022, 10:33 AM
  • 02 1400_02 1399_1132022_032840.mp4

Date
01/13/2022
W/O
0935772
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00349
PipeID
P02971
Time
2:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
H2081
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Maintenance Related
Project
20220113MDM_DISTRICT_2_INTERCEPTOR_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
02 1400
Downstream MH
02 1399
Dir. of Survey
Downstream
Length Surveyed
452.7 ft.
Total Length
452.7 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
36
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
36
Pipe schematic from manhole 02 1400 to 02 1399
MH: 02 1400MH: 02 1399downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE14.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG REBAR113.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - Open121.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped245.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped253.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open260.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR260.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR277.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR306 ft. SRC - Surface Reinforcement Corroded, from 01 to 04 o'clock, within 8 inches of joint: NO - BROKEN REBAR349.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Active356.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Active432.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR452.3 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR452.3 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR452.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG452.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE452.7 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM

Observation photos (9)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG REBAR

    14.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped

    121.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped

  • Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    260.1 ft. - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    277.6 ft. - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 04 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    306 ft. - Surface Reinforcement Corroded, from 01 to 04 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    432.8 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

Observations (25)

DistanceCodeObservation
452.3SRCLONG CIRCUM REBAR
452.3SRCLONG CIRCUM REBAR
260.1SRCLONG CIRCUM REBAR
245.7TFCCapped
0MWL
0MGOConn. @ Mh, 9 O' Clock. Active
2SAMSEVERE AGG
452.7AMH4:15AM
0MGOConn. @ Mh, 3 O' Clock. Capped
253.8TFOpen
2SRCLONG CIRCUM REBAR
306SRCBROKEN REBAR
452.3SAMSEVERE AGG
113.3TFOpen
121.2TFCCapped
260.1SRCLONG CIRCUM REBAR
349.1TFAActive
277.6SRCLONG CIRCUM REBAR
0AMH3:30AM
452.3SSSBLISTERING PEELING CONCRETE
0MWM
2SSSBLISTERING PEELING CONCRETE
356.8TFAActive
432.8SRCLONG CIRCUM REBAR
14.1SRCLONG REBAR

Properties (7)

additional_info
POST STROM EVALUATION
custom_field_three
LONG CIRCUM REBAR CORRODED & BROKEN
custom_field_two
1
customer
LACSD
datetime
2022-01-13T02:33:29-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false