Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2022, 08:30 AM
  • J 0059_J 0058_1102022_012803.mp4

Date
01/10/2022
W/O
0932055
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00062
PipeID
P11636
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2077
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20220110MDM_JOINT_OUTFALL_J_UNIT_2C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
J 0059
Downstream MH
J 0058
Dir. of Survey
Downstream
Length Surveyed
681.8 ft.
Total Length
681.8 ft.
Structural Index
4
Structural Quick
5344
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
33
Pipe schematic from manhole J 0059 to J 0058
MH: J 0059MH: J 0058downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 60% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING13.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING27.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING62.2 ft. MGO - General Observation - 70% MAG COAT FINISH97.3 ft. MGO - General Observation - 95% MAG COAT START259.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG394.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG652.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG681.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE681.1 ft. MGO - General Observation - 05% MAG COAT FINISH681.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG681.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED & MISSING681.8 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (10)

  • General Observation - MAG COAT 60% START

    2 ft. - General Observation - MAG COAT 60% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

    13.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

    27.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

  • General Observation - 95% MAG COAT START

    97.3 ft. - General Observation - 95% MAG COAT START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    259.2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    394.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    652.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (19)

DistanceCodeObservation
2MGOMAG COAT 60% START
681.1SSSBLISTERING PEELING CONCRETE
681.8AMH1:50AM
27.6SRCLONG CIRCUM REBAR CORRODED & MISSING
62.2MGO70% MAG COAT FINISH
652.6SAMSEVERE AGG
2SAMSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
681.1MGO05% MAG COAT FINISH
0MWL
13.1SRCLONG CIRCUM REBAR CORRODED & MISSING
394.4SAMSEVERE AGG
97.3MGO95% MAG COAT START
2SRCLONG CIRCUM REBAR CORRODED & MISSING
681.1SAMSEVERE AGG
0AMH12:55AM
259.2SAMSEVERE AGG
681.1SRCLONG CIRCUM REBAR CORRODED & MISSING
0MWM

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2022-01-10T00:30:54-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false