Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2021, 08:13 AM
  • B 1534_B 1533_12152021_002449.mp4

Date
12/15/2021
W/O
926782
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01200
PipeID
P26344
Time
12:13 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9633
Sewer Name
B JOINT OUTFALL B - UNIT 6J RELIEF
City
LA CANADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_926782_TV16116_DEC2021
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1534
Downstream MH
B 1533
Dir. of Survey
Downstream
Length Surveyed
244 ft.
Total Length
244 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
98
Pipe schematic from manhole B 1534 to B 1533
MH: B 1534MH: B 1533downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 15342 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start241.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish244 ft. AMH - Downstream Manhole, Survey Ends - B 1533

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2CL
0MWL
241.8DAGS
0MWM
244AMHB 1533
2DAGS
0AMHB 1534

Properties (8)

additional_info
630138121421202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-12-15T00:13:34-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40603