- Date
- 12/14/2021
- W/O
- 926772
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00091
- PipeID
- P08865
- Time
- 10:59 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9632
- Sewer Name
- B JOINT OUTFALL B - UNIT 5A
- City
- TEMPLE CITY
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 15
- Purpose
- Routine Assessment
- Project
- RFIR_WO_926772_TV15154_DEC2021
- Sewer Type
- Siphon
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 63 in.
- Upstream MH
- B 0353
- Downstream MH
- B 0352
- Dir. of Survey
- Downstream
- Length Surveyed
- 2 ft.
- Total Length
- 2 ft.
- Structural Index
- 4
- Structural Quick
- 5131
- Structural Rating
- 8
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole B 0353 to B 0352 Observation photos (3)

2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES