Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2021, 09:39 AM
  • 05 0375_05 2078_12102021_015209.mp4

Date
12/10/2021
W/O
921632
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05587
Time
1:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9561
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_921632_TV05325_NOV2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
33 in.
Upstream MH
05 0375
Downstream MH
05 2078
Dir. of Survey
Downstream
Length Surveyed
18.2 ft.
Total Length
18.2 ft.
Structural Index
3
Structural Quick
5133
Structural Rating
20
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 05 0375 to 05 2078
MH: 05 0375MH: 05 2078downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03750 ft. MWM - Water Mark, 30 %of cross sectional area4 ft. MGO - General Observation - MAG COAT4.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start4.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES18.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish18.2 ft. AMH - Downstream Manhole, Survey Ends - 05 027818.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    4.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    7.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
18.2AMH05 0278
7.8SRV
18.1SAP
4.7SSS
18.2SSS
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
0AMH05 0375
0MWM
4MGOMAG COAT
4.7SAP

Properties (7)

additional_info
630074120821201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/SPALLIN
custom_field_two
2
customer
1
datetime
2021-12-10T01:39:51-08:00
documentation
PROPIPE
is_lateral_inspection
false