Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2021, 09:02 AM
  • 05 0359_05 0358_12092021_012633.mp4

Date
12/09/2021
W/O
921632
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05573
Time
1:02 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9557
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_921632_TV05325_NOV2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0359
Downstream MH
05 0358
Dir. of Survey
Downstream
Length Surveyed
438 ft.
Total Length
438 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
435
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
435
Pipe schematic from manhole 05 0359 to 05 0358
MH: 05 0359MH: 05 0358downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 03590 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 25 %of cross sectional area3.8 ft. MGO - General Observation - MAG COAT3.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start437.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish438 ft. AMH - Downstream Manhole, Survey Begins - 05 0358438 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
437.9SSS
3.8MGOMAG COAT
438AMH05 0358
3.8SSS
0AMH05 0359
0MWM
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
3.8SAP
438SAP

Properties (7)

additional_info
630074120821201
custom_field_three
AGGREGATE PROJECTING/SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2021-12-09T01:02:11-08:00
documentation
PROPIPE
is_lateral_inspection
false