Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 09:18 AM
  • 02 1349_02 1348_11092021_014625.mp4

Date
11/09/2021
W/O
921735
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00277
PipeID
P04623
Time
1:18 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9529
Sewer Name
02 JANE STREET BRANCH TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921735_TV02342_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 1349
Downstream MH
02 1348
Dir. of Survey
Downstream
Length Surveyed
740.9 ft.
Total Length
740.9 ft.
Structural Index
3
Structural Quick
3T21
Structural Rating
320
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
322
Pipe schematic from manhole 02 1349 to 02 1348
MH: 02 1349MH: 02 1348downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1349201.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES205.1 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES215 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start289.7 ft. TS - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"564.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES573.4 ft. MGO - General Observation - LINK PIPE740.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish740.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1348

Observation photos (5)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    201.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    205.1 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    215 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    289.7 ft. - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 11 o'clock,  , within 8 inches of joint: YES

    564.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
740.9CM
564.2DAE
201.6CM
289.7TS
0MGOCONNECTION AT THE MH 9 OC'LOCK
215CM
0MWL
573.4MGOLINK PIPE
0MWM
0AMH02 1349
205.1CL
740.9AMH02 1348

Properties (7)

additional_info
630074110821202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-09T01:18:09-08:00
documentation
PROPIPE
is_lateral_inspection
false