Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 10:05 AM
  • 02 1351_02 1350_11092021_022044.mp4

Date
11/09/2021
W/O
921735
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00277
PipeID
P03874
Time
2:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9529
Sewer Name
02 JANE STREET BRANCH TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921735_TV02342_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
02 1350
Downstream MH
02 1351
Dir. of Survey
Upstream
Length Surveyed
409.2 ft.
Total Length
409.2 ft.
Structural Index
3
Structural Quick
3H11
Structural Rating
136
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
136
Pipe schematic from manhole 02 1350 to 02 1351
MH: 02 1350MH: 02 1351upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 13510.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK150 ft. TS - Tap Saddle, at 11 o'clock, -, within 8 inches of joint: NO, 6"224.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start377.9 ft. MGO - General Observation - ABANDONED MH406.1 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES409.2 ft. MWL - Water Level, 10 %of cross sectional area409.2 ft. AMH - Downstream Manhole, Survey Begins - 02 1350409.2 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (4)

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • General Observation - ABANDONED MH

    31.3 ft. - General Observation - ABANDONED MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    184.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    259.2 ft. - Tap Saddle, at 11 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
409.1CM
31.3MGOABANDONED MH
409.1MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
184.8CM
0AMH02 1350
0MWM
259.2TS
409.2AMH02 1351
3.1CC

Properties (7)

additional_info
630074110821202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-09T02:05:54-08:00
documentation
PROPIPE
is_lateral_inspection
false