- Date
- 12/10/2021
- W/O
- 926758
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00683
- PipeID
- P14132
- Time
- 1:11 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9625
- Sewer Name
- 18 LA MIRADA TRUNK, SECTS 1&2
- City
- SANTA FE SPRINGS
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- RFIR_WO_926758_TV18145_DEC2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 18 0300
- Downstream MH
- 18 0301
- Dir. of Survey
- Upstream
- Length Surveyed
- 450.4 ft.
- Total Length
- 450.4 ft.
- Structural Index
- 3
- Structural Quick
- 3Q2Q
- Structural Rating
- 445
- O&M Index
- 2
- O&M Quick
- 2X00
- O&M Rating
- 254
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 699
Pipe schematic from manhole 18 0300 to 18 0301 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - General Observation - 65% MAG COAT

449.7 ft. - General Observation - ROACHES @ MH