Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 06:19 AM
  • 02 1307_02 2045_11082021_223445.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04618
Time
10:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9528
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 1307
Downstream MH
02 2045
Dir. of Survey
Downstream
Length Surveyed
293.3 ft.
Total Length
293.3 ft.
Structural Index
3
Structural Quick
3K26
Structural Rating
199
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
199
Pipe schematic from manhole 02 1307 to 02 2045
MH: 02 1307MH: 02 2045downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13070 ft. MWM - Water Mark, 15 %of cross sectional area8.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES30.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.1 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES37 ft. SSS - Surface Spalling, from 10 to 01 o'clock, within 8 inches of joint: YES39 ft. SSS - Surface Spalling, from 10 to 01 o'clock, within 8 inches of joint: YES56 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES57.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES81.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"137 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"150 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK293.3 ft. AMH - Downstream Manhole, Survey Ends - 02 2045293.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    14.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    57.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    140.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (26)

DistanceCodeObservation
37SSS
293.3MGOCONNECTION AT THE MH 3 OC'LOCK
293.3AMH02 2045
14.7SSS
56FL
0MWL
150TF
30.2TFC
134.7TFC
57.7TB
140.1TB
282.8TF
231.6TF
65.1CL
39SSS
213.8TF
86.3TFC
293.3CM
31.1SSS
144.9TF
137TF
251.9TF
81.1TF
8.4CM
0AMH02 1307
0MWM

Properties (7)

additional_info
630074110821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T22:19:55-08:00
documentation
PROPIPE
is_lateral_inspection
false