Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 09:17 AM
  • 02 1323_02 1322_11042021_013056.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03845
Time
2:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
27 in.
Upstream MH
02 1322
Downstream MH
02 1323
Dir. of Survey
Upstream
Length Surveyed
345.9 ft.
Total Length
345.9 ft.
Structural Index
3
Structural Quick
3M21
Structural Rating
209
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
213
Pipe schematic from manhole 02 1322 to 02 1323
MH: 02 1322MH: 02 1323upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 02 13234.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES174.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"234.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.2 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"306.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.4 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"342.8 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES345.9 ft. MWM - Water Mark, 5 %of cross sectional area345.9 ft. MWL - Water Level, 5 %of cross sectional area345.9 ft. AMH - Downstream Manhole, Survey Begins - 02 1322

Observation photos (5)

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    12.5 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    42.7 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    117.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    171.5 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    178.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (21)

DistanceCodeObservation
3.1CM
223.4TFC
111.7TF
39.6TFC
173CL
277.5TF
171.5TBA
139.2TF
0MWM
0MWL
42.7TBI
178.8TB
345.9MGOCONNECTION AT THE MH 9 OC'LOCK
218.3TF
239TF
341.3TF
0AMH02 1322
290.5TF
117.2TB
345.9AMH02 1323
12.5TBI

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-04T02:17:45-07:00
documentation
PROPIPE
is_lateral_inspection
false