Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 08:52 AM
  • 02 1322_02 1321A_11042021_010840.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03844
Time
1:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
27 in.
Upstream MH
02 1322
Downstream MH
02 1321A
Dir. of Survey
Downstream
Length Surveyed
313 ft.
Total Length
313 ft.
Structural Index
3
Structural Quick
3K23
Structural Rating
193
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
193
Pipe schematic from manhole 02 1322 to 02 1321A
MH: 02 1322MH: 02 1321Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13220 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area3.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES5.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.1 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES96.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"169 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES169 ft. CS - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES206.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK313 ft. AMH - Downstream Manhole, Survey Ends - 02 1321A

Observations (17)

DistanceCodeObservation
206.3TF
313AMH02 1321A
75.9TF
0AMH02 1322
96.4TF
130.2TF
3.1CL
96.1CC
0MWM
64.6TF
312.9MGOCONNECTION AT THE MH 9 OC'LOCK
247.7TF
5.6TFC
169CL
244.7TF
169CS
0MWL

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-04T01:52:27-07:00
documentation
PROPIPE
is_lateral_inspection
false