Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 09:52 AM
  • 02 1320_02 1319_11042021_020340.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03840
Time
2:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
27 in.
Upstream MH
02 1319
Downstream MH
02 1320
Dir. of Survey
Upstream
Length Surveyed
276.9 ft.
Total Length
276.9 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1319 to 02 1320
MH: 02 1319MH: 02 1320upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 02 13200 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES182.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.8 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES259.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start276.9 ft. MWM - Water Mark, 15 %of cross sectional area276.9 ft. AMH - Downstream Manhole, Survey Begins - 02 1319276.9 ft. MWL - Water Level, 5 %of cross sectional area276.9 ft. MGO - General Observation - CONNECTION AT THE MH 6 OC'LOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
166.1CL
0MWM
276.9MGOCONNECTION AT THE MH 3 OC'LOCK
94.4TF
26.1CM
0AMH02 1319
0MWL
187.3TF
276.9AMH02 1320
276.9MGOCONNECTION AT THE MH 12 OC'LOCK
17CM
276.9CM
0MGOCONNECTION AT THE MH 6 OC'LOCK

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-04T02:52:42-07:00
documentation
PROPIPE
is_lateral_inspection
false