Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 10:57 AM
  • 02 1315_02 1314_11042021_030821.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03835
Time
3:57 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 1315
Downstream MH
02 1314
Dir. of Survey
Downstream
Length Surveyed
267.6 ft.
Total Length
267.6 ft.
Structural Index
3
Structural Quick
4136
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole 02 1315 to 02 1314
MH: 02 1315MH: 02 1314downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13150 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 5 %of cross sectional area3.9 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES5.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"41 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES55.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"111 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES119.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES164.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES177 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES182.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.1 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES205 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES205.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"243.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES259.2 ft. FM - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES267.6 ft. AOC - Drop Connection, Survey Ends - 02 1314

Observation photos (2)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    5.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

    259.2 ft. - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
98.8TF
164.1CL
205CC
259.2FM
267.6AOC02 1314
182.4TF
3.9CM
0MWM
177CC
41CM
55.6TFC
205.1TF
0AMH02 1315
101.5TF
195TF
119.2TF
111CM
243.1TFC
254CM
5.9TB
60.9TF
199.1CS
146.1CL
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-04T03:57:30-07:00
documentation
PROPIPE
is_lateral_inspection
false