Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 05:55 AM
  • 02 1308_02 1307A_11082021_221001.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03828
Time
9:55 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9528
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 1308
Downstream MH
02 1307A
Dir. of Survey
Downstream
Length Surveyed
330.2 ft.
Total Length
330.2 ft.
Structural Index
2
Structural Quick
3324
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
23
Pipe schematic from manhole 02 1308 to 02 1307A
MH: 02 1308MH: 02 1307Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13080 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.6 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES44.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.1 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES77.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.1 ft. CC - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES136 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES149 ft. CC - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES176.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES187.1 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES219.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES224.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"236 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES237.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES265.1 ft. CM - Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES271 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES273.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"291.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"319 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES330.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1307A330.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observations (32)

DistanceCodeObservation
149CC
100.2TF
319CL
265.1CM
226.8TFC
176.1CL
3.6CM
136TF
273.3TFC
134.1CC
138.7TFC
0MWL
224.6TF
77.4TFC
237.2TF
271CC
120.8TFC
236CL
0AMH02 1308
0MGOCONNECTION AT THE MH 9 OC'LOCK
44.2TFC
0MWM
330.2AMH02 1307A
291.2TFC
330.2MGOCONNECTION AT THE MH 9 OC'LOCK
62.1CC
219.1CL
0MGOCONNECTION AT THE MH 3 OC'LOCK
187.1CM
247.1CC
146.1CC
318.8TF

Properties (7)

additional_info
630074110821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T21:55:24-08:00
documentation
PROPIPE
is_lateral_inspection
false