Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 06:15 AM
  • 02 1307A_02 1307_11082021_221850.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03827
Time
10:15 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9528
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 1307A
Downstream MH
02 1307
Dir. of Survey
Downstream
Length Surveyed
11.9 ft.
Total Length
11.9 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 1307A to 02 1307
MH: 02 1307AMH: 02 1307downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1307A0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. TBB - Tap Break-In Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"3.1 ft. CC - Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES6.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1307

Observation photos (2)

  • Tap Break-In Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"

    3.1 ft. - Tap Break-In Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    6.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (8)

DistanceCodeObservation
0MWM
0AMH02 1307A
0MGOCONNECTION AT THE MH 9 OC'LOCK
6.6TB
11.9AMH02 1307
3.1TBB
3.1CC
0MWL

Properties (7)

additional_info
630074110821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T22:15:22-08:00
documentation
PROPIPE
is_lateral_inspection
false