Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 04:47 AM
  • 02 1932_02 1931_11032021_205952.mp4

Date
11/03/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04705
Time
9:47 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 1932
Downstream MH
02 1931
Dir. of Survey
Downstream
Length Surveyed
288 ft.
Total Length
288 ft.
Structural Index
2
Structural Quick
3324
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 02 1932 to 02 1931
MH: 02 1932MH: 02 1931downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 19320 ft. MWM - Water Mark, 20 %of cross sectional area87.1 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES112.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES117.8 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES133.1 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES199 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES199 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES222.1 ft. MWL - Water Level, 30 %of cross sectional area231 ft. MWL - Water Level, 45 %of cross sectional area240 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES246.1 ft. MWL - Water Level, 30 %of cross sectional area257 ft. MWL - Water Level, 20 %of cross sectional area288 ft. AMH - Downstream Manhole, Survey Ends - 02 1931

Observation photos (2)

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    87.1 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    112.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
199CL
117.8CM
231MWL
112.8CL
257MWL
222.1MWL
246.1MWL
87.1CM
240CL
0MWL
288AMH02 1931
0AMH02 1932
0MWM
133.1CM
199CL

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-03T21:47:45-07:00
documentation
PROPIPE
is_lateral_inspection
false