Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 05:42 AM
  • 02 1926_02 1925_11032021_220830.mp4

Date
11/03/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04274
Time
10:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1926
Downstream MH
02 1925
Dir. of Survey
Downstream
Length Surveyed
249.9 ft.
Total Length
249.9 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
21
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole 02 1926 to 02 1925
MH: 02 1926MH: 02 1925downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 19265.1 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES28.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES33 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES162 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES238.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start238.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start244.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish249.9 ft. MGO - General Observation - LARGE WOOD BLOCK IN MH249.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1925249.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

    5.1 ft. - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    28.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    33 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    162 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    238.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - LARGE WOOD BLOCK IN MH

    249.9 ft. - General Observation - LARGE WOOD BLOCK IN MH

Observations (13)

DistanceCodeObservation
238.9FM
0MWL
0MWM
249.9MGOLARGE WOOD BLOCK IN MH
5.1FC
249.9AMH02 1925
28.1CL
244.1CL
249.9FM
238.1CL
33CL
0AMH02 1926
162CM

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE FRACTURE'S/CRACKS
custom_field_two
2
customer
1
datetime
2021-11-03T22:42:23-07:00
documentation
PROPIPE
is_lateral_inspection
false