Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 06:58 AM
  • 02 1922_02 1921_11032021_230905.mp4

Date
11/03/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04270
Time
11:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1922
Downstream MH
02 1921
Dir. of Survey
Downstream
Length Surveyed
201.2 ft.
Total Length
201.2 ft.
Structural Index
3
Structural Quick
4E3B
Structural Rating
168
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
168
Pipe schematic from manhole 02 1922 to 02 1921
MH: 02 1922MH: 02 1921downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 19220 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area4.1 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES6.8 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"9.1 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES9.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.6 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES29.1 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES32.9 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.1 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES63.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.4 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES77 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES77.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish83.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES153.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES186.3 ft. TS - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"188 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES201.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1921201.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (9)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    6.8 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    15.6 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    32.9 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    36.1 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    66.4 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    84.1 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    186.3 ft. - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (25)

DistanceCodeObservation
63.5TF
186.3TS
0AMH02 1922
83.5TFC
0MWL
29.1CM
36.1FM
32.9TS
9.1CC
201.2AMH02 1921
77.2CM
66.4FC
201.2MGOCONNECTION AT THE MH 3 OC'LOCK
77CM
84.1TBA
188CC
5FM
153.1FC
6.8TS
0MWM
4.1CM
9.9CM
134.5TF
15.6FM
137.1CL

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-03T23:58:30-07:00
documentation
PROPIPE
is_lateral_inspection
false