Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 07:44 AM
  • 02 1919_02 1918_11032021_235224.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04267
Time
12:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
02 1918
Downstream MH
02 1919
Dir. of Survey
Upstream
Length Surveyed
197.7 ft.
Total Length
197.7 ft.
Structural Index
4
Structural Quick
4F32
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
156
Pipe schematic from manhole 02 1918 to 02 1919
MH: 02 1918MH: 02 1919upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 19199.6 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES9.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES13.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES45.6 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES66.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.7 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES153.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES173.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES197.7 ft. MWL - Water Level, 5 %of cross sectional area197.7 ft. AMH - Downstream Manhole, Survey Begins - 02 1918197.7 ft. MWM - Water Mark, 15 %of cross sectional area

Observations (13)

DistanceCodeObservation
24.1CL
152.1FM
0MWL
188.1CC
92.6TF
0AMH02 1918
75CC
44.5FL
188.1FL
131.4TF
197.7AMH02 1919
0MWM
184CL

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-04T00:44:32-07:00
documentation
PROPIPE
is_lateral_inspection
false