Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 07:30 AM
  • 02 1918_02 1917_11032021_234212.mp4

Date
11/04/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P04266
Time
12:30 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9526
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
02 1918
Downstream MH
02 1917
Dir. of Survey
Downstream
Length Surveyed
128.5 ft.
Total Length
128.5 ft.
Structural Index
4
Structural Quick
4D33
Structural Rating
121
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
124
Pipe schematic from manhole 02 1918 to 02 1917
MH: 02 1918MH: 02 1917downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 19180 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area3.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.1 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES30.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.1 ft. CC - Crack Circumferential, from 08 to 05 o'clock, within 8 inches of joint: YES32 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES52.1 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES58.1 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES59.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.1 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES93 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"94 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES104.3 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES113.5 ft. FM - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES116.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES128.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK128.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1917128.5 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    123.2 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0AMH02 1918
93TFC
128.5AMH02 1917
31.1CC
123.2DSZ
0MWM
32FL
104.3CL
13.1RFJ
128.4MGOCONNECTION AT THE MH 3 OC'LOCK
116.3TFC
3.9FM
30.3TF
0MWL
52.1CC
128.5MGOCONNECTION AT THE MH 12 OC'LOCK
59.6TF
113.5FM
94FL
128.4FM
58.1FM
75.1CM

Properties (7)

additional_info
630074110321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-04T00:30:19-07:00
documentation
PROPIPE
is_lateral_inspection
false