Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 07:05 AM
  • 02 1305A_02 1305_11082021_232035.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03825
Time
11:05 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9528
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1305
Downstream MH
02 1305A
Dir. of Survey
Upstream
Length Surveyed
221.3 ft.
Total Length
221.3 ft.
Structural Index
2
Structural Quick
3325
Structural Rating
21
O&M Index
1
O&M Quick
1H00
O&M Rating
44
Overall Index
1
Overall Quick
Overall Rating
65
Pipe schematic from manhole 02 1305 to 02 1305A
MH: 02 1305MH: 02 1305Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 1305A0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK12.2 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES17.2 ft. CC - Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES20.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES25.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES39.2 ft. CC - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES103.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES121.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES146.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.3 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR187.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR193.2 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR199.3 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR205.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES218.2 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES221.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK221.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK221.3 ft. MWL - Water Level, 15 %of cross sectional area221.3 ft. MWM - Water Mark, 15 %of cross sectional area221.3 ft. AMH - Downstream Manhole, Survey Begins - 02 1305

Observations (23)

DistanceCodeObservation
196.1CL
0MGOCONNECTION AT THE MH 3 OC'LOCK
51RFJ
22RFJ
221.3AMH02 1305A
204.1CC
15CL
118CL
209.1CM
0MGOCONNECTION AT THE MH 9 OC'LOCK
75TF
61.2TF
15.6TFC
221.3MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
28.1RFJ
182.1CC
100.1CL
3.1CM
0MWM
201CL
34RFJ
0AMH02 1305

Properties (5)

additional_info
630074110821201
customer
1
datetime
2021-11-08T23:05:12-08:00
documentation
PROPIPE
is_lateral_inspection
false