Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2021, 05:15 AM
  • 02 1301_02 1300_11082021_212657.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03818
Time
9:15 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9528
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1301
Downstream MH
02 1300
Dir. of Survey
Downstream
Length Surveyed
219.9 ft.
Total Length
219.9 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
132
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
132
Pipe schematic from manhole 02 1301 to 02 1300
MH: 02 1301MH: 02 1300downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13010 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.1 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES21.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"36.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish219.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1300219.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    112.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    194.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (20)

DistanceCodeObservation
9.1CM
121.2TFC
3.2CM
0AMH02 1301
64.6TF
67.7TF
219.9CM
0MWM
182.4TF
112.9TB
21.1TF
0MWL
194.6TB
189.7TFC
36.5TF
74.7TF
115.6TF
219.9AMH02 1300
219.9MGOCONNECTION AT THE MH 3 OC'LOCK
79.2TF

Properties (7)

additional_info
630074110821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T21:15:11-08:00
documentation
PROPIPE
is_lateral_inspection
false