Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2021, 10:24 AM
  • 02 1292_02 1291_11082021_023940.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03809
Time
2:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9527
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1292
Downstream MH
02 1291
Dir. of Survey
Downstream
Length Surveyed
331.6 ft.
Total Length
331.6 ft.
Structural Index
2
Structural Quick
4236
Structural Rating
45
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 02 1292 to 02 1291
MH: 02 1292MH: 02 1291downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12922.9 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES19.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES52.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES59.1 ft. CC - Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES63.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.1 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES101.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES160 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES183.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES196.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.3 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES213.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES226 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES228.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"270 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES274.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start279.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish280 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES282 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES287.1 ft. CM - Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES306.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"313 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES315.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES320.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES331.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1291

Observation photos (6)

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    74.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    103.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    212.3 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    228.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    234.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    270.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (44)

DistanceCodeObservation
0MWL
228.8TB
0MWM
63.1TF
320.1CL
185.8TF
224CC
103.5TFC
47.1CL
114.7TF
24.8TF
313CL
228.9TFC
270.8FM
331.6AMH02 1291
74.3TB
274.1CL
103.5TB
306.1TF
213.8TF
19.6TF
287.1CM
196.2TF
127CC
183.2TF
270TF
226CC
59.1CC
231.7TFC
282CL
0AMH02 1292
52.1CM
111.8TF
279.1CL
234.7TB
212.3FM
65.5TF
193CM
280CM
101.8TFC
160CC
83.1CM
315.1CL
2.9CM

Properties (7)

additional_info
630074110821001
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T02:24:34-08:00
documentation
PROPIPE
is_lateral_inspection
false