Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2021, 10:20 AM
  • 02 1280_02 1279_11082021_012853.mp4

Date
11/08/2021
W/O
921813
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03795
Time
2:20 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9527
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921813_TV02239_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
02 1280
Downstream MH
02 1279
Dir. of Survey
Downstream
Length Surveyed
325.3 ft.
Total Length
325.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 02 1280 to 02 1279
MH: 02 1280MH: 02 1279downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12800 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK6.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start256.4 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1279

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    256.4 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (8)

DistanceCodeObservation
256.4TS
0MWM
0AMH02 1280
6.8CM
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
325.3AMH02 1279
324.9CM

Properties (7)

additional_info
630074110821001
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-08T02:20:00-08:00
documentation
PROPIPE
is_lateral_inspection
false