Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2021, 09:24 AM
  • 04 0073_04 0072_10042021_024516.mp4

Date
10/04/2021
W/O
916396
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11809
Time
2:24 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9398
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_916396_TV04022_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0072
Downstream MH
04 0073
Dir. of Survey
Upstream
Length Surveyed
157.8 ft.
Total Length
157.8 ft.
Structural Index
3
Structural Quick
3B22
Structural Rating
49
O&M Index
2
O&M Quick
3521
O&M Rating
31
Overall Index
2
Overall Quick
Overall Rating
80
Pipe schematic from manhole 04 0072 to 04 0073
MH: 04 0072MH: 04 0073upstream0 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - DUE TO ROOTS0.4 ft. RMC - Roots Medium Connection, from 12 to 06 o'clock, 40 %, within 8 inches of joint: YES0.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"7.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6"21.3 ft. RMC - Roots Medium Connection, from 12 to 06 o'clock, 30 %, within 8 inches of joint: YES21.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start56.3 ft. RTJ - Roots Tap Joint, from 06 to 10 o'clock, 20 %, within 8 inches of joint: YESR57.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN76.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start91.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"91.3 ft. RFC - Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES91.6 ft. RFJ - Roots Fine Joint, from 02 to 10 o'clock, within 8 inches of joint: YESR98.7 ft. RFC - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: NO98.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"108.6 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES108.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"111.3 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES111.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES149.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.9 ft. RFC - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES152.9 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES152.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES157.8 ft. AMH - Downstream Manhole, Survey Begins - 04 0072157.8 ft. MWL - Water Level, 5 %of cross sectional area157.8 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (14)

  • Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

    4.9 ft. - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

    7.9 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    16.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

    46.5 ft. - Roots Medium Connection, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

    49.2 ft. - Roots Medium Connection, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: NO

    59.1 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Roots Fine Joint, from 02 to 10 o'clock, within 8 inches of joint: YESR

    66.2 ft. - Roots Fine Joint, from 02 to 10 o'clock, within 8 inches of joint: YESR

  • Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES

    66.5 ft. - Roots Fine Connection, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    81.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Tap Joint, from 06 to 10 o'clock, 20 %, within 8 inches of joint: YESR

    101.5 ft. - Roots Tap Joint, from 06 to 10 o'clock, 20 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    109.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Roots Medium Connection, from 12 to 06 o'clock, 30 %, within 8 inches of joint: YES

    136.5 ft. - Roots Medium Connection, from 12 to 06 o'clock, 30 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 12 to 06 o'clock, 40 %, within 8 inches of joint: YES

    157.4 ft. - Roots Medium Connection, from 12 to 06 o'clock, 40 %, within 8 inches of joint: YES

  • Survey Abandoned - DUE TO ROOTS

    157.8 ft. - Survey Abandoned - DUE TO ROOTS

Observations (30)

DistanceCodeObservation
157.8RFJ
66.2RFJ
59.1RFC
46.5RMC
136.5RMC
59.1TF
136.5TFA
100.5TFOPEN
7.9TFA
4.9RMC
150TBA
4CL
66.5TBA
157.4RMC
7.9RFC
0AMH04 0072
157.8CM
109.2RFJ
0MWL
0MWM
4.9TFA
49.2RMC
101.5RTJ
157.8MSADUE TO ROOTS
49.2TFA
157.4TF
81.3CM
46.5TFA
16.5CL
66.5RFC

Properties (7)

additional_info
630069100421001
custom_field_three
ABANDONED DUE TO ROOTS
custom_field_two
5
customer
1
datetime
2021-10-04T02:24:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false