Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2021, 07:22 AM
  • 02 1367_02 1366_11092021_233831.mp4

Date
11/09/2021
W/O
921562
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00277
PipeID
P03890
Time
11:22 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9530
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
WO_921562_TV02072_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
02 1367
Downstream MH
02 1366
Dir. of Survey
Downstream
Length Surveyed
317.1 ft.
Total Length
317.1 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
319
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
319
Pipe schematic from manhole 02 1367 to 02 1366
MH: 02 1367MH: 02 1366downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13672 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"21.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN42.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN62.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"116.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES260.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"315 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317 ft. MGO - General Observation - ROACHES @ MH317.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1366

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    222.4 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
42.5TFOPEN
0MWL
222.4FM
0MGOROACHES @ MH
219TF
116.1TF
315SSS
21.2TFOPEN
0MWM
317.1CM
0AMH01 1367
2SSS
317.1AMH02 1366
291.8TF
271.4TF
14.2TFA
317MGOROACHES @ MH
187.3TF
2CM
62.1TFA
140.3TF
175.7TF
119.9TF
260.1TF

Properties (7)

additional_info
630074110921201
custom_field_three
MULTIPLE CRACKS/SPALLING
custom_field_two
3
customer
1
datetime
2021-11-09T23:22:36-08:00
documentation
PROPIPE
is_lateral_inspection
false