- Date
- 10/28/2021
- W/O
- 916725
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00156
- PipeID
- P10002
- Time
- 11:35 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9514
- Sewer Name
- D JOINT OUTFALL D - UNIT 6
- City
- LAWNDALE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 17
- Purpose
- Routine Assessment
- Project
- WO_916725_TV05166_OCT2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 39 in.
- Width
- 60 in.
- Upstream MH
- 05 0338
- Downstream MH
- A 1041
- Dir. of Survey
- Upstream
- Length Surveyed
- 17.3 ft.
- Total Length
- 17.3 ft.
- Structural Index
- 3
- Structural Quick
- 5131
- Structural Rating
- 14
- O&M Index
- 3
- O&M Quick
- 3300
- O&M Rating
- 9
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 23
Pipe schematic from manhole 05 0338 to A 1041 Observation photos (4)

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

2.1 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE/DEBRIS

2.1 ft. - General Observation - 45% MAG COAT

13.7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES