Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2021, 08:59 AM
  • 32 0233_32 0232_10212021_021040.mp4

Date
10/21/2021
W/O
916876
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00914
PipeID
P20549
Time
1:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9469
Sewer Name
32 DISTRICT #32 MAIN RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_916876_TV32014_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
32 0233
Downstream MH
32 0232
Dir. of Survey
Downstream
Length Surveyed
458.2 ft.
Total Length
458.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Q00
O&M Rating
182
Overall Index
2
Overall Quick
Overall Rating
182
Pipe schematic from manhole 32 0233 to 32 0232
MH: 32 0233MH: 32 0232downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 02330 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start456.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish458.2 ft. AMH - Downstream Manhole, Survey Ends - 32 0232

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0AMH32 0233
0MWL
2DAGS
0MWM
458.2AMH32 0232
456.1DAGS

Properties (8)

additional_info
630069102021201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-10-21T01:59:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
33660