Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2021, 07:59 AM
  • F 0314_F 0313_12102021_001602.mp4

Date
12/09/2021
W/O
921505
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00046
PipeID
P23212
Time
11:59 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9559
Sewer Name
F JOINT OUTFALL F - UNIT 7D
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_921505_TV18080_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
F 0314
Downstream MH
F 0313
Dir. of Survey
Downstream
Length Surveyed
275.4 ft.
Total Length
275.4 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
155
O&M Index
3
O&M Quick
413J
O&M Rating
163
Overall Index
3
Overall Quick
Overall Rating
318
Pipe schematic from manhole F 0314 to F 0313
MH: F 0314MH: F 0313downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 031412.2 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start21.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start275 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - THROUGHOUT THE REACH275 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES - THROUGHOUT THE REACH275.4 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish275.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK275.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.4 ft. AMH - Downstream Manhole, Survey Ends - F 0313

Observation photos (2)

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    12.2 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
275SSSTHROUGHOUT THE REACH
275.4DAE
275.4MGOCONNECTION AT THE MH 3 OC'LOCK
21.5CM
275.4CM
275.4AMHF 0313
275DAGSTHROUGHOUT THE REACH
0MWL
0MWM
0AMHF 0314
12.2DAE

Properties (8)

additional_info
630074120821203
custom_field_three
CRACKS/ENCRUSTATION/GREASE/SPALLING
custom_field_two
3
customer
1
datetime
2021-12-09T23:59:05-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37328