Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2021, 11:39 AM
  • B 0392_B 0391_12172021_035035.mp4

Date
12/17/2021
W/O
0931355
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00091
PipeID
P08904
Time
3:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2054
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20211217MDM_JOINT_B_UNIT_5A
Material
NRCP
Shape
Circular
Height
21 in.
Upstream MH
B 0392
Downstream MH
B 0391
Dir. of Survey
Downstream
Length Surveyed
268.8 ft.
Total Length
268.8 ft.
Structural Index
3
Structural Quick
4222
Structural Rating
12
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole B 0392 to B 0391
MH: B 0392MH: B 0391downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT98% START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE108.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE148.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG268.3 ft. MGO - General Observation - MAG COAT 98% FINISH268.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT268.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG268.8 ft. AMH - Downstream Manhole, Survey Ends - 4:05AM

Observation photos (5)

  • General Observation - MAG COAT98% START

    2 ft. - General Observation - MAG COAT98% START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    108.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    148.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (12)

DistanceCodeObservation
2MGOMAG COAT98% START
2SAMSEVERE AGG
0MWM
268.3MGOMAG COAT 98% FINISH
2SSSBLISTERING PEELING CONCRETE
268.3SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
108.8SSSBLISTERING CONCRETE
148.2SAMSEVERE AGG
0AMH3:45AM
268.3SAMSEVERE AGG
268.8AMH4:05AM
0MWL

Properties (6)

custom_field_three
SEVERE AGG MISSING-98% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2021-12-17T03:39:01-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false