Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2021, 09:13 AM
  • 30 0186_30 0185_10192021_023204.mp4

Date
10/19/2021
W/O
916326
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00860
PipeID
P17887
Time
2:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9450
Sewer Name
30 EL PORTO TRUNK
City
MANHATTAN BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
01
Purpose
Routine Assessment
Project
WO_916326_TV30002_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0185
Downstream MH
30 0186
Dir. of Survey
Upstream
Length Surveyed
371.2 ft.
Total Length
371.2 ft.
Structural Index
3
Structural Quick
4N3N
Structural Rating
657
O&M Index
2
O&M Quick
312P
O&M Rating
175
Overall Index
3
Overall Quick
Overall Rating
832
Pipe schematic from manhole 30 0185 to 30 0186
MH: 30 0185MH: 30 0186upstream0 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 30 01862.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish33.4 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - BROKEN CONN/OPEN69.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish69.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN134.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start367.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start369.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start369.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start369.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start371.2 ft. MWL - Water Level, 20 %of cross sectional area371.2 ft. MWM - Water Mark, 25 %of cross sectional area371.2 ft. AMH - Downstream Manhole, Survey Begins - 30 0185

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    236.9 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    301.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 4", 6" - BROKEN CONN/OPEN

    337.8 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - BROKEN CONN/OPEN

Observations (16)

DistanceCodeObservation
2SSS
337.8TBDBROKEN CONN/OPEN
301.7DSZ
236.9DSZ
369CM
2DAGS
3.9FM
371.2FM
0MWL
369DAGS
0MWM
2CM
371.2AMH30 0186
0AMH30 0185
301.7TBOPEN
369SSS

Properties (7)

additional_info
630074101821201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-10-19T02:13:25-07:00
documentation
PROPIPE
is_lateral_inspection
false