Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 11:09 AM
  • 08 0477_08 0645_11022021_031752.mp4

Date
11/02/2021
W/O
916504
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00025
PipeID
P20118
Time
4:09 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9520
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_916504_TV08140_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0477
Downstream MH
08 0645
Dir. of Survey
Downstream
Length Surveyed
13.9 ft.
Total Length
13.9 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole 08 0477 to 08 0645
MH: 08 0477MH: 08 0645downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04772.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish13.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish13.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0645 ZOOMED IN

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - 08 0645 ZOOMED IN

    13.9 ft. - Downstream Manhole, Survey Ends - 08 0645 ZOOMED IN

Observations (8)

DistanceCodeObservation
0MWL
2.9SAP
0MWM
4.2SRV
0AMH08 0477
13.8SRV
13.9AMH08 0645 ZOOMED IN
13.8SAP

Properties (7)

additional_info
630074110121204
custom_field_three
REINFORCEMENT VISIBLE/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-11-02T04:09:44-07:00
documentation
PROPIPE
is_lateral_inspection
false