Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 07:58 AM
  • H 0899_H 0647_09282021_011450.mp4

Date
09/28/2021
W/O
916309
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00192
PipeID
P16434
Time
12:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9385
Sewer Name
H JOINT OUTFALL H - UNIT 8J
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_916309_TV22085_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
H 0899
Downstream MH
H 0647
Dir. of Survey
Downstream
Length Surveyed
383.9 ft.
Total Length
383.9 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
228
O&M Index
2
O&M Quick
412N
O&M Rating
156
Overall Index
3
Overall Quick
Overall Rating
384
Pipe schematic from manhole H 0899 to H 0647
MH: H 0899MH: H 0647downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 08992 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.9 ft. MGO - General Observation - MAG COATING THROUGHOUT138.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"339 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"343.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"381.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish381.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish383.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK383.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE383.9 ft. AMH - Downstream Manhole, Survey Ends - H 0647

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    103.9 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    383.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
0MWL
154.7TFA
289.5TFA
383.9MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SAP
23.8TFA
383.9MGOCOCKROACHES IN MANHOLE
339TFA
191.1TFA
88.5TFA
343.1TFA
103.9MGOMAG COATING THROUGHOUT
72.7TFA
2DAGS
381.6DAGS
215.6TFC
0MWM
138.4TFA
381.6SAP
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMHH 0899
383.9AMHH 0647

Properties (7)

additional_info
630069092721203
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-09-28T00:58:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false