Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2021, 05:39 PM
Date
12/09/2021
W/O
0926416
Weather
Heavy Rain
Operator/Surveyor
SHADLER
Sewer ID
Z00594
PipeID
P12627
Time
9:39 AM
Certificate
U-415-06024035
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
IO380
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20211209KS_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
15 0849
Downstream MH
15 0848
Dir. of Survey
Downstream
Length Surveyed
210.8 ft.
Total Length
210.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0849 to 15 0848
MH: 15 0849MH: 15 0848downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:03 AM0 ft. MWL - Water Level, 15 %of cross sectional area74.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"98.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - OPEN155.5 ft. RFC - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES - 15% ROOTS155.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 15% ROOTS165 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - POSSIBLE ABANDONED / BLOCKED201.5 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4", 4" - 85% ROOTS-LATERAL/ACTIVE208.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"210.8 ft. AOC - Drop Connection, Survey Ends - 11:00 AM

Observations (11)

DistanceCodeObservation
0MWM
98.4TFOPEN
74.2TFA
165TFPOSSIBLE ABANDONED / BLOCKED
210.8AOC11:00 AM
208.3TFA
0AMH10:03 AM
155.5RFC15% ROOTS
155.5TFA15% ROOTS
201.5TFD85% ROOTS-LATERAL/ACTIVE
0MWL

Properties (9)

additional_info
POST ROOT EVALUATION
custom_field_three
LINED
custom_field_two
4
customer
LACSD
datetime
2021-12-09T09:39:10-08:00
documentation
SHADLER, FRANKLIN
is_lateral_inspection
false
lining
CIPP
year_laid
20020918