Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2021, 05:45 PM
Date
12/03/2021
W/O
PENDING
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00349
PipeID
P02991
Time
9:45 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0378
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Maintenance Related
Project
20211203MI_DISTRICT_2_INTERCEPTOR_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
02 1420
Downstream MH
02 1419
Dir. of Survey
Downstream
Length Surveyed
44.3 ft.
Total Length
44.3 ft.
Structural Index
4
Structural Quick
5B37
Structural Rating
100
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
100
Pipe schematic from manhole 02 1420 to 02 1419
MH: 02 1420MH: 02 1419downstream0 ft. MGO - General Observation - AIR LINES INSIDE MH0 ft. MGO - General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON0 ft. AMH - Upstream Manhole, Survey Begins - 11:55 AM0 ft. MWL - Water Level, 100 %of cross sectional area8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN8 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start8 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start15.7 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start23 ft. SRC - Surface Reinforcement Corroded, from 07 to 05 o'clock, within 8 inches of joint: YES, Start39.9 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - BROKEN40 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROEKN/MISSING44.3 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish44.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish44.3 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish44.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish44.3 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON44.3 ft. SRC - Surface Reinforcement Corroded, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observations (17)

DistanceCodeObservation
0MGOAIR LINES INSIDE MH
0MGOVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
23SRC
44.3SRV
8TFOPEN
0AMH11:55 AM
40SRCBROEKN/MISSING
44.3SSS
8SAP
44.3SAP
44.3SRC
8SSS
44.3MSAVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
15.7SRV
39.9SRCBROKEN
44.3SRC
0MWL

Properties (7)

additional_info
VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_three
SPALLING/AGGREGATE/MISSING/BROKEN REBAR
custom_field_two
1
customer
LACSD
datetime
2021-12-03T09:45:02-08:00
documentation
IGNACIO, BRAR, MIRANDA
is_lateral_inspection
false