Search
Uploads
Inspections
Wastewater/Activity/PacpInspection/1.0
Dec 3, 2021, 05:40 PM
Date
12/03/2021
W/O
PENDING
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00349
PipeID
P02991
Time
9:40 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
—
Pre-Cleaning
Not Known
Media Label
I0378
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Maintenance Related
Project
20211203MI_DISTRICT_2_INTERCEPTOR_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1419
Downstream MH
02 1420
Dir. of Survey
Upstream
Length Surveyed
123 ft.
Total Length
123 ft.
Structural Index
2
Structural Quick
4134
Structural Rating
40
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
—
Overall Rating
40
Pipe schematic from manhole 02 1419 to 02 1420
MH: 02 1419
MH: 02 1420
upstream
0 ft. AMH - Upstream Manhole, Survey Ends - 11:02 AM
0.8 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish
3.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES
10 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES
10 ft. MGO - General Observation - GASKET MATERIAL HANGING/LOOSE AT JOINT
59.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start
59.9 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES
96.6 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES
103 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES
115 ft. MGO - General Observation - MAG COAT
123 ft. MGO - General Observation - NORTH AIRLINE INSPECTION ONLY
123 ft. MWL - Water Level, 0 %of cross sectional area - DRY LINE
123 ft. AMH - Downstream Manhole, Survey Begins - 10:41 AM
All inspections of P02991
Work order PENDING
Observations (13)
Distance
Code
Observation
63.1
SSS
—
0
MGO
NORTH AIRLINE INSPECTION ONLY
113
CM
—
123
AMH
11:02 AM
63.1
CM
—
26.4
CM
—
113
MGO
GASKET MATERIAL HANGING/LOOSE AT JOINT
0
MWL
DRY LINE
8
MGO
MAG COAT
119.5
FM
—
0
AMH
10:41 AM
122.2
SSS
—
20
CM
—
Properties (7)
additional_info
NORTH WEST AIRLINE INSPECTION ONLY
custom_field_three
SPALLING/CRACKS/FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-12-03T09:40:40-08:00
documentation
IGNACIO, BRAR, MIRANDA
is_lateral_inspection
false