Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2021, 05:38 PM
Date
12/03/2021
W/O
PENDING
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00349
PipeID
P02991
Time
9:38 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0378
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Maintenance Related
Project
20211203MI_DISTRICT_2_INTERCEPTOR_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1419
Downstream MH
02 1420
Dir. of Survey
Upstream
Length Surveyed
123.4 ft.
Total Length
123.4 ft.
Structural Index
2
Structural Quick
4234
Structural Rating
65
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
65
Pipe schematic from manhole 02 1419 to 02 1420
MH: 02 1419MH: 02 1420upstream0 ft. AMH - Upstream Manhole, Survey Ends - 10:26 AM0.1 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish2.9 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES9.2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES9.2 ft. MGO - General Observation - POSSIBLE MAGNESIUM HYDROXIDE COAT THROUGHOUT15.7 ft. CM - Crack Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES30.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES46.8 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES53.3 ft. JOM - Joint Offset Medium - 1/4"53.3 ft. MGO - General Observation - GASKET LOOSE/HANGING53.6 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES111 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start121.4 ft. MGO - General Observation - NORTH AIRLINE INSPECTION ONLY123.4 ft. MWL - Water Level, 0 %of cross sectional area - DRY LINE123.4 ft. AMH - Downstream Manhole, Survey Begins - 10:00

Observations (15)

DistanceCodeObservation
69.8CM
0MWLDRY LINE
114.2FM
12.4SSS
0AMH10:00
92.9FM
70.1JOM1/4"
114.2MGOPOSSIBLE MAGNESIUM HYDROXIDE COAT THROUGHOUT
2MGONORTH AIRLINE INSPECTION ONLY
107.7CM
120.5CM
123.4AMH10:26 AM
70.1MGOGASKET LOOSE/HANGING
76.6CM
123.3SSS

Properties (7)

additional_info
NORTH AIRLINE INSPECTION ONLY
custom_field_three
SPALLING/CRACKS/FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-12-03T09:38:02-08:00
documentation
IGNACIO, BRAR, MIRANDA
is_lateral_inspection
false