- Date
- 10/12/2021
- W/O
- 916511
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00706
- PipeID
- P14662
- Time
- 3:11 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9441
- Sewer Name
- 18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
- City
- SANTA FE SPRINGS
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_916511_TV18182_OCT2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 18 0801
- Downstream MH
- 18 0802A
- Dir. of Survey
- Upstream
- Length Surveyed
- 456.5 ft.
- Total Length
- 456.5 ft.
- Structural Index
- 4
- Structural Quick
- 514K
- Structural Rating
- 322
- O&M Index
- 2
- O&M Quick
- 2D11
- O&M Rating
- 49
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 371
Pipe schematic from manhole 18 0801 to 18 0802A Observation photos (6)

5.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

7.1 ft. - Roots Fine Barrell, from 12 to 01 o'clock, Start

30.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

148 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES, Start

172.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

257.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start