Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 07:41 AM
  • H 0900_H 0899_09282021_005308.mp4

Date
09/28/2021
W/O
916634
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00192
PipeID
P16435
Time
12:41 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9386
Sewer Name
H JOINT OUTFALL H - UNIT 8J
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_916634_TV22153_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
H 0900
Downstream MH
H 0899
Dir. of Survey
Downstream
Length Surveyed
225.9 ft.
Total Length
225.9 ft.
Structural Index
3
Structural Quick
3H27
Structural Rating
146
O&M Index
2
O&M Quick
412H
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
238
Pipe schematic from manhole H 0900 to H 0899
MH: H 0900MH: H 0899downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 09002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start8.7 ft. MWM - Water Mark, 50 %of cross sectional area16.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"80 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94 ft. MGO - General Observation - MAG COATING THROUGHOUT102.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"152 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.3 ft. TFA - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start224.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish224.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish224.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish225.9 ft. AMH - Downstream Manhole, Survey Ends - H 0899225.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    94 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    187.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
224.2SAP
2DAGS
160.3TFA
80TBA
8.7MWM
94MGOMAG COATING THROUGHOUT
225.9AMHH 0899
102.7TFA
90.5TFC
16.2TFC
224.2SSS
0MWL
187.7SSS
225.9MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SAP
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
152TFA
0MGOCOCKROACHES IN MANHOLE
0AMHH 0900
224.2DAGS

Properties (7)

additional_info
630069092721204
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-09-28T00:41:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false