Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2021, 08:30 AM
  • 05 1700_05 1699_12112021_005315.mp4

Date
12/11/2021
W/O
0926575
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06926
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2041
Sewer Name
05 LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20211208MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1700
Downstream MH
05 1699
Dir. of Survey
Downstream
Length Surveyed
224.7 ft.
Total Length
224.7 ft.
Structural Index
2
Structural Quick
4431
Structural Rating
101
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
101
Pipe schematic from manhole 05 1700 to 05 1699
MH: 05 1700MH: 05 1699downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT12.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE27.2 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL30 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL33.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL48.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL61.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL64 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H66.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H70.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL73.1 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL85.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL88.6 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL94.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL97.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL100.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL103.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL109.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL112.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL115.9 ft. FC - Fracture Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES - SL118.6 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL121.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL125.5 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - SLIGHT128.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H130.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL134.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL143 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL146.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL149.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL154.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL158.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL161.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL174.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H182.7 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES185.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL188.5 ft. SRP - Surface Reinforcement Projecting, from 08 to 12 o'clock, within 8 inches of joint: YES - SL191.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES195 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - SL197.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H204.5 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - H206.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL209.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL213.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL215.9 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - SL219.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL221.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL224 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active224.7 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    70.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    94.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    206.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

Observations (51)

DistanceCodeObservation
70.2FMSL
221.7FCSL
33.5FCSL
206.8FMSL
103.4FCSL
12.3FCHAIRLINE
48.6FCSL
182.7FC
158.2FCSL
213.1FCSL
224.7AMH1:20AM
112.5FCSL
109.5FCSL
191.5FC
30FCSL
219.5FCSL
224MGOConn. @ Mh, 9 O' Clock. Active
85.6FCSL
197.7FCH
215.9FCSL
73.1FCSL
0AMH12:35AM
161.7FCSL
188.5SRPSL
0MWL
154.8FCSL
134.2FCSL
61.2FCSL
27.2FCSL
146.2FCSL
0MWM
88.6FCSL
185.8FCSL
115.9FCSL
128.2FCH
209.8FCSL
64FCH
195FCSL
66.9FCH
2FCSLIGHT
204.5FCH
118.6FCSL
149.8FCSL
143FCSL
97.4FMSL
125.5FCSLIGHT
121.7FCSL
174.1FCH
130.8FCSL
100.7FCSL
94.1FMSL

Properties (6)

custom_field_three
SLIGHT FRACTURES MULTIPLE AT JOINTS
custom_field_two
2
customer
LACSD
datetime
2021-12-11T00:30:47-08:00
documentation
MARTIN,OLIVER 111,REVELES
is_lateral_inspection
false