Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 12, 2021, 06:03 AM
  • 16 0553_16 0552_10112021_231332.mp4

Date
10/11/2021
W/O
916508
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00659
PipeID
P13604
Time
11:03 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9438
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_916508_TV16077_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0553
Downstream MH
16 0552
Dir. of Survey
Downstream
Length Surveyed
101.5 ft.
Total Length
101.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
60
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
60
Pipe schematic from manhole 16 0553 to 16 0552
MH: 16 0553MH: 16 0552downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05530 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.3 ft. MGO - General Observation - MAG COAT2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"88 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101 ft. MGO - General Observation - Surface Spalling throughout the reach, from 9 to 3 oclock101.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK101.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0552101.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
90.9TF
0AMH16 0553
0MWM
101.5MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
88TFC
101.5AMH16 0552
101.5SAP
2.3MGOMAG COAT
38.2TF
101MGOSurface Spalling throughout the reach, from 9 to 3 oclock
2.3SAP

Properties (7)

additional_info
630074101121201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-10-11T23:03:53-07:00
documentation
PROPIPE
is_lateral_inspection
false