Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2021, 08:55 AM
  • J 0117_J 0116_1282021_012341.mp4

Date
12/08/2021
W/O
0926956
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00065
PipeID
P11696
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2040
Sewer Name
J JOINT OUTFALL J - UNIT 3
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Capital Improvement Program Assesment
Project
20211208MDM_JOINT_OUTFALL_J_UNIT_3
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
J 0117
Downstream MH
J 0116
Dir. of Survey
Downstream
Length Surveyed
42 ft.
Total Length
42 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole J 0117 to J 0116
MH: J 0117MH: J 0116downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM10.5 ft. FC - Fracture Circumferential, from 05 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT13.7 ft. FC - Fracture Circumferential, from 05 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT30.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES40.6 ft. JSM - Joint Separated Medium - SEALED42 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (1)

  • Fracture Circumferential, from 05 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    10.5 ft. - Fracture Circumferential, from 05 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

Observations (8)

DistanceCodeObservation
30.5DAGS
0MWM
40.6JSMSEALED
0MWL
13.7FCSLIGHT
0AMH12:55AM
42AMH1:10AM
10.5FCSLIGHT

Properties (6)

custom_field_three
SLIGHT CIRCUM FRACTURE 3' LONG
custom_field_two
2
customer
LACSD
datetime
2021-12-08T00:55:29-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false